4.14.5 14-4* Energy Optimizing
Parameters for adjusting the energy optimization level in both variable torque (VT) and automatic energy optimization (AEO) mode
in
parameter 1-03 Torque Characteristics
.
Parameter 14-40 VT Level
Table 497: Parameter 14-40 VT Level
14-40 VT Level
Default value: 66%
Parameter type: Range, 40 - 90%
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
N O T I C E
This parameter is not active when
parameter 1-10 Motor Construction
is set to
[1] PM non-salient SPM
.
Enter the level of motor magnetization at low speed. Selection of a low value reduces energy loss in the motor but also reduces load
capability.
Parameter 14-41 AEO Minimum Magnetisation
Table 498: Parameter 14-41 AEO Minimum Magnetisation
14-41 AEO Minimum Magnetisation
Default value: Size related
Parameter type: Range, 30 - 200%
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: True
N O T I C E
This parameter is not active when
parameter 1-10 Motor Construction
is set to
[1] PM non-salient SPM
.
Enter the minimum allowable magnetization for AEO. Selection of a low value reduces energy loss in the motor but can also reduce
resistance to sudden load changes.
Parameter 14-42 Minimum AEO Frequency
Table 499: Parameter 14-42 Minimum AEO Frequency
14-42 Minimum AEO Frequency
Default value: Size related
Parameter type: Range, 0 - 255 Hz
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: True
N O T I C E
This parameter is not active when
parameter 1-10 Motor Construction
is set to
[1] PM non-salient SPM
.
Enter the minimum frequencyat which the automatic energy optimization (AEO)is to be active.
Parameter 14-43 Motor Cosphi
Table 500: Parameter 14-43 Motor Cosphi
14-43 Motor Cosphi
Default value: Size related
Parameter type: Range, 0 - 255 Hz
Setup: All setups
Conversion index: -2
Data type: Uint16
Change during operation: True
AU373327181955en-000101 / 130R1208 | 275
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide