is used to reduce these voltage ripples in the DC link. In general, DC-link compensation is recommended for most applications, but
pay attention when operating in field weakening as it can generate speed oscillations at the motor shaft. In field weakening, turn off
DC-link compensation.
Option
Name
Description
[0]
Off
Disables DC-link compensation.
[1]*
On
Enables DC-link compensation.
Parameter 14-52 Fan Control
Table 508: Parameter 14-52 Fan Control
14-52 Fan Control
Default Value: [0] Auto
Parameter Type: Option
Setup: All set-ups
Conversion Index: -
Data Type: Uint8
Change during operation: True
Select the minimum speed of the main fan.
Op-
tion
Name
Description
[0]*
Auto
Select
[0] Auto
to run fan only when internal temperature in the drive is in the range 35 °C (95 °F) to ap-
proximately 55 °C (131 °F). The fan runs at low speed below 35 °C (95 °F), and at full speed at approxi-
mately 55 °C (131 °F).
[1]
On 50%
The fan always runs at 50% speed or above. The fan runs at 50% speed at 35 °C (95 °F), and at full speed at
approximately 55 °C (131 °F).
[2]
On 75%
The fan always runs at 75% speed or above. The fan runs at 75% speed at 35 °C (95 °F), and at full speed at
approximately 55 °C (131 °F).
[3]
On 100%
The fan always runs at 100% speed.
[4]
Auto (Low
temp env.)
This option is the same as
[0] Auto
, but with special considerations around and below 0 °C (32 °F). In op-
tion
[0] Auto
there is a risk that the fan starts running around 0 °C as the drive detects a sensor fault and
thus protects the drive while reporting
warning 66, Heat sink Temperature Low
. Option
[4] Auto (Low temp
env.)
can be used in very cold environments and prevents the negative effects of this further cooling and
avoids
warning 66, Heat sink Temperature Low
.
Parameter 14-53 Fan Monitor
Table 509: Parameter 14-53 Fan Monitor
14-53 Fan Monitor
Default Value: [1] Warning
Parameter Type: Option
Setup: All set-ups
Conversion Index: -
Data Type: Uint8
Change during operation: True
Select the drive action if a fan fault is detected.
Option
Name
Description
[0]
Disabled
[1]*
Warning
[2]
Trip
AU373327181955en-000101 / 130R1208
278 | Danfoss A/S © 2021.08
Parameter Descriptions