Option
Name
Description
[47]
Czech
Part of language package 3.
[48]
Polski
Part of language package 4.
[49]
Russian
Part of language package 3.
[50]
Thai
Part of language package 2.
[51]
Bahasa Indonesia
Part of language package 2.
Parameter 0-02 Motor Speed Unit
Table 10: Parameter 0-02 Motor Speed Unit
0-02 Motor Speed Unit
Default value: –
Parameter type: Option
Setup: 2 setups
Conversion index: –
Data type: Uint8
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
N O T I C E
Changing the motor speed unit resets certain parameters to their initial value. Select the motor speed unit before modifying oth-
er parameters.
The information shown in the display depends on the settings in
parameter 0-02 Motor Speed Unit
and
parameter 0-03 Regional Set-
tings
. The default settings of
parameter 0-02 Motor Speed Unit
and
parameter 0-03 Regional Settings
depend on the region to which
the drive is supplied.
Option
Name
Description
[0]
RPM
Select to show motor speed variables and parameters using motor speed (RPM).
[1]
Hz
Select to show motor speed variables and parameters using output frequency (Hz).
Parameter 0-03 Regional Settings
Table 11: Parameter 0-03 Regioanl Settings
0-03 Regional Settings
Default value: –
Parameter type: Option
Setup: 2 setups
Conversion index: –
Data type: Uint8
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
Option Name
Description
[0]
International Activate
parameter 1-20 Motor Power [kW]
for setting the motor power in kW and set the default value of
parameter 1-23 Motor Frequency
to 50 Hz.
[1]
US
Activate
parameter 1-20 Motor Power [kW]
for setting the motor power in hp and set the default value of
parameter 1-23 Motor Frequency
to 60 Hz.
AU373327181955en-000101 / 130R1208
32 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide