View the type code string for the option installed in slot C and a translation of the type code string. For example, for type code string
CXXXX
, the translation is
No option
.
Parameter 15-75 Slot C0/E0 Option SW Version
Table 568: Parameter 15-75 Slot C0/E0 Option SW Version
15-75 Slot C0/E0 Option SW Version
Default Value: 0
Parameter Type: Range, 0 - 20
Setup: All set-ups
Conversion Index: 0
Data Type: VisStr[20]
Change during operation: False
View the software version for the option installed in slot C.
Parameter 15-76 Option in Slot C1/E1
Table 569: Parameter 15-76 Option in Slot C1/E1
15-76 Option in Slot C1/E1
Default Value: 0
Parameter Type: Range, 0 - 30
Setup: All set-ups
Conversion Index: 0
Data Type: VisStr[30]
Change during operation: False
Shows the type code string for the option in slot C1 (
CXXXX
if no option) and the translation, that is
No option
.
Parameter 15-77 Slot C1/E1 Option SW Version
Table 570: Parameter 15-77 Slot C1/E1 Option SW Version
15-77 Slot C1/E1 Option SW Version
Default Value: 0
Parameter Type: Range, 0 - 20
Setup: All set-ups
Conversion Index: 0
Data Type: VisStr[20]
Change during operation: False
Shows the software version for the installed option in option slot C.
4.15.12 15-8* Operating Data II
Parameter 15-80 Fan Running Hours
Table 571: Parameter 15-80 Fan Running Hours
15-80 Fan Running Hours
Default Value: 0 h
Parameter Type: Range, 0 - 2147483647 h
Setup: All set-ups
Conversion Index: 74
Data Type: Uint32
Change during operation: True
View for how many hours the heat sink fan has run (increments for every hour). The value is saved when the drive is turned off.
Parameter 15-81 Preset Fan Running Hours
Table 572: Parameter 15-81 Preset Fan Running Hours
15-81 Preset Fan Running Hours
Default Value: 0 h
Parameter Type: Range, 0 - 99999 h
Setup: All set-ups
Conversion Index: 74
Data Type: Uint32
Change during operation: True
Enter the preset fan running hours counter, see
parameter 15-80 Fan Running Hours
. This parameter cannot be selected via the serial
port RS485.
AU373327181955en-000101 / 130R1208
300 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide