Table 520: Selection of Action when Selected Alarm Appears
Failure
Alarm Element in param-
eter 14-90 F ault
Level
Off Warning Trip Trip lock Trip with de-
layed reset
10 V low
1
1490.0
X
D
–
–
–
24 V supply low
47
1490.1
X
–
–
D
–
1.8 V supply low
48
1490.2
X
–
–
D
–
Voltage level
64
1490.3
X
D
–
–
–
Ground fault during ramping
14
1490.4
–
–
D
X
–
Ground fault 2 during continuous operation 45
1490.5
–
–
D
X
–
Torque limit
12
1490.6
X
D
–
–
–
Overcurrent
13
1490.7
–
–
X
D
–
Short circuit
16
1490.8
–
–
X
D
–
Heat sinke temperature
29
1490.9
–
–
X
D
–
Heat sink sensor
39
1490.10
–
–
X
D
–
Control card temperature
65
1490.11
–
–
X
D
–
Power card temperature
69
1490.12
–
(1)
X
D
–
Heat sink temperature
(2)
244
1490.13
–
–
X
D
–
Heat sink sensor
(2)
245
1490.14
–
–
X
D
–
Power card temperature
(2)
247
1490.15
–
–
X
D
–
Motor phase U missing
30
1490.16
–
–
X
D
–
Motor phase V missing
31
1490.16
–
–
X
D
–
Motor phase W missing
32
1490.16
–
–
X
D
–
Current limit
(3)
59
1490.19
X
D
–
–
–
Locked rotor
99
1490.20
–
–
D
X
–
1
In small and medium power drives, alarm 69, Power card temperature is only a warning.
2
Only high-power drives.
3
Warning 59 is configured in 1490.19. The current limit warning can be disabled by choice. The alarm cannot be configured.
VLT® Motion Control Tool MCT 10 has the element numbers listed in the column ID. Use this table with MCT 10 to get information
about specific fault levels.
AU373327181955en-000101 / 130R1208 | 283
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide