Option
Name
Description
[0]*
Timed actions auto
Enable timed actions.
[1]
Timed actions disabled
Disable timed actions, normal operation according to control commands.
[2]
Constant on actions
Disable timed actions. Constant on actions are activated.
[3]
Constant off actions
Disable timed actions. Constant off actions are activated.
Parameter 23-09 Timed Actions Reactivation
Table 684: Parameter 23-09 Timed Actions Reactivation
23-09 Timed Actions Reactivation
Default Value: [1] Enabled
Parameter Type: Option
Setup: 2 setups
Conversion Index: -
Data Type: Uint8
Change during operation: True
Option Name
Description
[0]
Disabled After an update of:
power cycling
setting date
time
change of summertime
change of Hand Auto mode
change of Constant On and Off
set-up change where all activated ON actions are overridden to OFF actions until passing the next time
for an ON action. Any OFF actions remain unchanged.
[1]*
Enabled
After an update of time/condition On and OFF actions are immediately set to the actual time programming
of ON and OFF actions.
T imed A c tion
ON: RUN
OFF : ST OP
Po w e r
C y cle
P23-09:
Disabled
Po w e r
C y cle
P23-09:
Disabled
P23-09:
Disable
Enable
Po w e r
C y cle
P23-09:
Enabled
Sta tus
RUNNING
ST OPPED
e3
0b
b8
08
.1
1
Illustration 85: Example of Reactivation Test
4.19.2 23-1* Maintenance
Wear and tear calls for periodic inspection and service of elements in the application, for example motor bearings, feedback sensors,
seals, and filters. With preventive maintenance, the service intervals may be programmed into the drive. The drive gives a message
when maintenance is required. 20 preventive maintenance events can be programmed into the drive.
AU373327181955en-000101 / 130R1208 | 329
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide