Parameter 0-14 Readout: Edit Set-ups/Channel
Table 18: Parameter 0-14 Readout: Edit Set-ups/Channel
0-14 Readout: Edit Set-ups/Channel
Default value: 0
Parameter type: Range [-2147483648–2147483648]
Setup: All setups
Conversion index: 0
Data type: Int32
Change during operation: True
View the setting of
parameter 0-11 Edit Set-up
for each of the 4 different communication channels. When the number is shown as a
hex number, as it is in the LCP, each number represents 1 channel. Numbers 1–4 represent a setup number; F means factory setting;
and A means active setup. The channels are, from right to left: LCP, FC bus, USB, HPFB1-5.
Example
The number AAAAAA21h means the following:
The drive received the setting of setup 2 via a fieldbus channel. The selection is reflected in
parameter 0-11 Edit Set-up
.
A user selected setup 1 via the LCP.
All other channels are using the active setup.
Parameter 0-15 Readout: Actual Set-up
Table 19: Parameter 0-15 Readout: Actual Set-up
0-15 Readout: Actual Set-up
Default value: 0
Parameter type: Range [0–255]
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: False
Makes it possible to read out the active setup, also when
[9] Multi Set-up
is selected in
parameter 0-10 Active Set-up
.
4.1.3 0-2* LCP Display
Define the variables shown in the LCP.
For information on how to write display texts, refer to:
Parameter 0-37 Display Text 1.
Parameter 0-38 Display Text 2.
Parameter 0-39 Display Text 3.
Parameter 0-20 Display Line 1.1 Small
Table 20: Parameter 0-20 Display Line 1.1 Small
0-20 Display Line 1.1 Small
Default value: –
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint16
Change during operation: True
Select a variable for display in line 1, left position.