N O T I C E
Parameter 1-50 Motor Magnetisation at Zero Speed
has no effect when
parameter 1-10 Motor Construction
=
[1] PM, nonsalient SPM
.
Use this parameter along with
parameter 1-51 Min Speed Normal Magnetising [RPM]
to obtain a different thermal load on the motor
when running at low speed. Enter a value which is a percentage of the rated magnetizing current. If the setting is too low, the
torque on the motor shaft may be reduced.
Magn. current
e
3
0
b
a
0
4
5
.1
2
Hz
Par.1-50
Par.1-51
100%
Par.1-52
RPM
Illustration 29: Motor Magnetization
Parameter 1-51 Min Speed Normal Magnetising [RPM]
Table 104: Parameter 1-51 Min Speed Normal Magnetising [RPM]
1-51 Min Speed Normal Magnetising [RPM]
Default value: Size related
Parameter type: Range, 10 - 600 RPM
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: True
N O T I C E
Parameter 1-51 Min Speed Normal Magnetising [RPM]
has no effect when
parameter 1-10 Motor Construction
=
[1] PM, nonsalient
SPM
.
Set the required speed for normal magnetizing current. If the speed is set lower than the motor slip speed,
parameter 1-50 Motor
Magnetisation at Zero Speed
and
parameter 1-51 Min Speed Normal Magnetising [RPM]
are of no significance. Use this parameter
along with
parameter 1-50 Motor Magnetisation at Zero Speed
.
Parameter 1-52 Min Speed Normal Magnetising [Hz]
Table 105: Parameter 1-52 Min Speed Normal Magnetising [Hz]
1-52 Min Speed Normal Magnetising [Hz]
Default value: Size Related
Parameter type: Range, 0 - 250.0 Hz
Setup: All setups
Conversion index: -1
Data type: Uint16
Change during operation: True
Set the required frequency for normal magnetizing current. If the frequency is set lower than the motor slip frequency,
parameter
1-50 Motor Magnetisation at Zero Speed
is inactive. Use this parameter along with
parameter 1-50 Motor Magnetisation at Zero Speed
.
Parameter 1-53 Model Shift Frequency
Table 106: Parameter 1-53 Model Shift Frequency
1-53 Model Shift Frequency
Default value: Size related
Parameter type: Range, 4 - 18.0 Hz
Setup: All setups
Conversion index: -1
Data type: Uint16
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
Flux model shift:
Enter the frequency value for shifting between 2 models for determining motor speed. Select the value based on
settings in
parameter 1-00 Configuration Mode
and
parameter 1-01 Motor Control Principle
.There are the following options:
AU373327181955en-000101 / 130R1208 | 77
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide