Option Name
Description
[105]
Torque relate to
rated
The torque is related to the motor torque setting.
[106]
Power
Taken from
parameter 1-20 Motor Power [kW]
.
[107]
Speed
Taken from
parameter 3-03 Maximum Reference
. 20 mA equals the value in
parameter 3-03 Maximum
Reference
.
[108]
Torque
Torque reference related to 160% torque.
[109]
Max out freq
0 Hz = 0 mA,
parameter 4-19 Max Output Frequency
= 20 mA.
[113]
PID clamped
output
[119]
Torque % lim
[130]
Output freq. 4–
20mA
0 Hz = 4 mA, 100 Hz = 20 mA.
[131]
Reference 4–
20mA
Parameter 3-00 Reference Range [Min-Max]
0% = 4 mA; 100% = 20 mA
Parameter 3-00 Reference Range [-Max-Max]
-100% = 4 mA; 0% = 12 mA; +100% = 20 mA.
[132]
Feedback 4–
20mA
[133]
Motor cur. 4–
20mA
The value is taken from
parameter 16-37 Inv. Max. Current
. The inverter maximum current (160% cur-
rent) is equal to 20 mA. Example: Inverter normal current (11 kW) is 24 A. 160% = 38.4 A. Motor
normal current is 22 A, the readout is 11.46 mA.
16 mA × 22
A
38 . 4
A
= 13 . 17 mA
If the normal motor current is equal to 20 mA, the output setting of
parameter 6-52 Terminal 42 Out-
put Max Scale
is:
I
VLT, MAX
× 100
I
Motor, Nom
= 38 . 4 × 100
22
= 175 %
[134]
Torq.% lim 4–20
mA
The torque setting is related to the setting in
parameter 4-16 Torque Limit Motor Mode
.
[135]
Torq.% nom 4–
20mA
The torque setting is related to the motor torque setting.
[136]
Power 4–20mA
Taken from
parameter 1-20 Motor Power [kW]
.
[137]
Speed 4–20mA
Taken from
parameter 3-03 Maximum Reference
. 20 mA = value in
parameter 3-03 Maximum Refer-
ence
.
[138]
Torque 4–20mA
Torque reference related to 160% torque.
[139]
Bus ctrl. 0-20mA
An output value set from fieldbus process data. The output works independently of internal func-
tions in the drive.
[140]
Bus ctrl. 4-20mA
An output value set from fieldbus process data. The output works independently of internal func-
tions in the drive.
[141]
Bus ctrl 0-20mA
t.o.
Parameter 4-54 Warning Reference Low
defines the behavior of the analog output in case of fieldbus
timeout.
AU373327181955en-000101 / 130R1208 | 185
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide