N O T I C E
This parameter cannot be adjusted while the motor is running.
Enter the nominal motor power in kW according to the motor nameplate data. The default value corresponds to the nominal rated
output of the drive. This parameter is visible in the LCP if
parameter 0-03 Regional Settings
is set to
[0] International
.
Parameter 1-21 Motor Power [HP]
Table 78: Parameter 1-21 Motor Power [HP]
1-21 Motor Power [HP]
Default value: Size related
Parameter type: Range, 0.09 - 3000.00 hp
Setup: All setups
Conversion index: -2
Data type: Uint32
Change during operation: False
Enter the nominal motor power in hp according to the motor nameplate data. The default value corresponds to the nominal rated
output of the drive. This parameter is visible in the LCP if
parameter 0-03 Regional Settings
is set to
[1] US
.
Parameter 1-22 Motor Voltage
Table 79: Parameter 1-22 Motor Voltage
1-22 Motor Voltage
Default value: Size related
Parameter type: Range, 10 - 1000 V
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: False
Enter the nominal motor voltage according to the motor nameplate data. The default value corresponds to the nominal rated out-
put of the unit.
Parameter 1-23 Motor Frequency
Table 80: Parameter 1-23 Motor Frequency
1-23 Motor Frequency
Default value: 50 Hz
Parameter type: Range, 20 - 1000 Hz
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: False
N O T I C E
From software version 6.72 onwards, the output frequency of the drive is limited to 590 Hz.
Select the motor frequency value from the motor nameplate data. If a value other than 50 Hz or 60 Hz is selected, adapt the load-
independent settings in
parameter 1-50 Motor Magnetisation at Zero Speed
to
parameter 1-53 Model Shift Frequency
. For 87 Hz opera-
tion with 230/400 V motors, set the nameplate data for 230 V/50 Hz. To run at 87 Hz, adapt
parameter 4-13 Motor Speed High Limit
[RPM]
and
parameter 3-03 Maximum Reference
.
Parameter 1-24 Motor Current
Table 81: Parameter 1-24 Motor Current
1-24 Motor Current
Default value: Size related
Parameter type: Range, 0.1 - 10000.00 A
Setup: All setups
Conversion index: -2
Data type: Uint32
Change during operation: False
Enter the nominal motor current value from the motor nameplate data. The data is used for calculating torque, motor overload
protection, and so on.
AU373327181955en-000101 / 130R1208 | 67
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide