Parameter 8-34 Estimated Cycle Time
Table 426: Parameter 8-34 Estimated Cycle Time
8-34 Estimated Cycle Time
Default value: 0 ms
Parameter type: Range, 0 - 1000000 ms
Setup: 2 setups
Conversion index: -3
Data type: Uint32
Change during operation: True
In noisy environments, the interface may be blocked due to overload or bad frames. This parameter specifies the time between 2
consecutive frames on the network. If the interface does not detect valid frames in that time, it flushes the receive buffer.
Parameter 8-35 Minimum Response Delay
Table 427: Parameter 8-35 Minimum Response Delay
8-35 Minimum Response Delay
Default value: 10 ms
Parameter type: Range, 1 - 10000 ms
Setup: 1 setup
Conversion index: -3
Data type: Uint16
Change during operation: True
Specify the minimum delay time between receiving a request and transmitting a response. This is used for overcoming modem
turnaround delays.
Parameter 8-36 Max Response Delay
Table 428: Parameter 8-36 Max Response Delay
8-36 Max Response Delay
Default value: Size related
Parameter type: Range, 11 - 10001 ms
Setup: 1 setup
Conversion index: -3
Data type: Uint16
Change during operation: True
Specify the maximum allowed delay time between transmitting a request and receiving a response. If a response from the drive
exceeds the time setting, then it is discarded.
Parameter 8-37 Max Inter-Char Delay
Table 429: Parameter 8-37 Max Inter-Char Delay
8-37 Max Inter-Char Delay
Default value: Size related
Parameter type: Range, 0.00 - 35.00 ms
Setup: 1 setup
Conversion index: -5
Data type: Uint16
Change during operation: True
Specify the maximum allowed time interval between receipt of 2 bytes. This parameter activates timeout if transmission is interrup-
ted. This parameter is active only when
parameter 8-30 Protocol
is set to
[1] FC MC protocol
.
4.9.4 8-4* FC MC Protocol Set
Parameter 8-40 Telegram Selection
Table 430: Parameter 8-40 Telegram Selection
8-40 Telegram Selection
Default value: [1] Standard telegram 1
Parameter type: Option
Setup: 2 setups
Conversion index: –
Data type: Uint8
Change during operation: True
Option
Name
Description
[1]*
Standard telegram 1
Enables use of freely configurable telegrams or standard telegrams for the FC port.
[100]
None
AU373327181955en-000101 / 130R1208 | 215
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide