The options for this parameter are the same as those listed for
parameter 5-10 Terminal 18 Digital Input
.
Parameter 5-18 Terminal X30/4 Digital Input
Table 298: Parameter 5-18 Terminal X30/4 Digital Input
5-18 Terminal X30/4 Digital Input
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
The options for this parameter are the same as those listed for
parameter 5-10 Terminal 18 Digital Input
.
Parameter 5-19 Terminal 37 Safe Stop
Table 299: Parameter 5-19 Terminal 37 Safe Stop
5-19 Terminal 37 Safe Stop
Default value: Size related
Parameter type: Option
Setup: 1 setup
Conversion index: –
Data type: Uint8
Change during operation: True
Use this parameter to configure the Safe Torque Off functionality. A warning message makes the drive coast the motor and enables
the automatic restart. An alarm message makes the drive coast the motor and requires a manual restart (via a fieldbus, Digital I/O, or
by pressing [RESET] on the LCP).
Option Name
Description
[1]
Safe stop alarm
Coasts the drive when Safe Torque Off is activated. Manual reset from LCP, digital input, or fieldbus.
[3]
Safe stop warn-
ing
Coasts the drive when Safe Torque Off is activated (terminal 37 off). When the Safe Torque Off circuit
is re-established, the drive continues without manual reset.
N O T I C E
Selecting Auto Reset/Warning enables automatic restart of the drive.
Table 300: Overview of Functions, Alarms, and Warnings
Function
Number
PTC
Relay
No function
[0]
–
–
Safe Torque Off alarm
[1]*
–
Safe Torque Off [A68
(1)
]
Safe Torque Off warning
[3]
–
Safe Torque Off [W68
(1)
]
1
W means warning and A means alarm.
A dangerous failure related to STO issues
alarm 72, Dangerous Failure
.
Parameter 5-20 Terminal X46/1 Digital Input
Table 301: Parameter 5-20 Terminal X46/1 Digital Input
5-20 Terminal X46/1 Digital Input
Default value: [0] No operation
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
All functions are described in
,
.
AU373327181955en-000101 / 130R1208 | 153
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide