Parameter 8-55 Set-up Select
Table 443: Parameter 8-55 Set-up Select
8-55 Set-up Select
Default value: [3] Logic OR
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the trigger for the set-up selection.
Option
Name
Description
[0]
Digital input
A digital input triggers the set-up selection.
[1]
Bus
A serial communication port or the fieldbus triggers the set-up selection.
[2]
Logic AND
The fieldbus/serial communication port and a digital input trigger the set-up selection.
[3]*
Logic OR
The fieldbus/serial communication port or a digital input triggers the set-up selection.
Parameter 8-56 Preset Reference Select
Table 444: Parameter 8-56 Preset Reference Select
8-56 Preset Reference Select
Default value: [3] Logic OR
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the trigger for the preset reference selection.
Option
Name
Description
[0]
Digital input
A digital input triggers the preset reference selection.
[1]
Bus
A serial communication port or the fieldbus triggers the preset reference selection.
[2]
Logic AND
The fieldbus/serial communication port and a digital input trigger the preset reference selection.
[3]*
Logic OR
The fieldbus/serial communication port or a digital input triggers the preset reference selection.
Parameter 8-57 PROFIdrive OFF2 Select
Table 445: Parameter 8-57 PROFIdrive OFF2 Select
8-57 PROFIdrive OFF2 Select
Default value: [3] Logic OR
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select control of the drive OFF2 selection via the terminals (digital input) and/or via the fieldbus. This parameter is active only when
parameter 8-01 Control Site
is set to
[0] Digital and ctrl. word
and
parameter 8-10 Control Word Profile
is set to
[1] PROFIdrive profile
.
Option
Name
Description
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]*
Logic OR
AU373327181955en-000101 / 130R1208
226 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide