Option
Name
Description
[10063]
Mech brake low alarm
[10065]
Controlboard overtemp alarm
[10067]
Option config changed alarm
[10068]
Safe stop alarm
[10069]
Powercard temp alarm
[10073]
Safestop auto restart alarm
[10074]
PTC thermistor alarm
[10075]
Illegal profile alarm
[10078]
Tracking error alarm
[10079]
Illegal PS config alarm
[10081]
CSIV corrupt alarm
[10082]
CSIV param error alarm
[10090]
Feedback monitor alarm
[10091]
AI54 settings alarm
Parameter 8-19 Product Code
Table 421: Parameter 8-19 Product Code
8-19 Product Code
Default value: Size related
Parameter type: Range, 0 - 2147483647, Array [2]
Setup: 1 setup
Conversion index: 0
Data type: Uint32
Change during operation: True
Select 0 to read out the actual fieldbus product code according to the mounted fieldbus option. Select 1 to read out the actual
vendor ID.
4.9.3 8-3* FC Port Settings
Parameter 8-30 Protocol
Table 422: Parameter 8-30 Protocol
8-30 Protocol
Default value: [0] FC
Parameter type: Option
Setup: 1 setup
Conversion index: –
Data type: Uint8
Change during operation: True
Select the protocol to be used. Changing protocol is not effective until after powering off the drive.
AU373327181955en-000101 / 130R1208 | 213
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide