Parameter 40-51 Flux Sensorless Corr. Gain
Table 739: Parameter 40-51 Flux Sensorless Corr. Gain
40-51 Flux Sensorless Corr. Gain
Default Value: Size related
Parameter Type: Range, 0.1 - 200.0
Setup: All set-ups
Conversion Index: -1
Data Type: Uint32
Change during operation: True
Adjust the flux correction gain used at low speed.
4.23 Parameter Group 43-** Unit Readouts
The parameters in this group provide readouts for monitoring the operation of drives in enclosure sizes D–F.
4.23.1 43-0* Component Status
This parameter group contains read-only information on hardware components in the power section. All parameters in this group
are arrays:
[0]: Power card 1 (the master power card in a parallel drive, or the only power card in a drive with a single inverter section).
[1]: Power card 2 (inverter connection in a parallel drive).
[2]: Power card 3 (inverter connection in a parallel drive).
[3]: Power card 4 (inverter connection in a parallel drive).
[4]: Power card 5 (rectifier connection in a parallel drive).
[5]: Power card 6 (rectifier connection in a parallel drive).
[6]: Power card 7 (rectifier connection in a parallel drive).
[7]: Power card 8 (rectifier connection in a parallel drive).
[8]: Inrush card (optional).
[9]: Fan power card 1 (optional).
[10]: Fan power card 2 (optional).
Parameter 43-00 Component Temp.
Table 740: Parameter 43-00 Component Temp.
43-00 Component Temp.
Default Value: 0 °C
Parameter Type: Range, -128 - 127 °C, Array [18]
Setup: All set-ups
Conversion Index: 100
Data Type: Int8
Change during operation: True
Shows the temperature of a system component. The elements of the array reference local PCB temperature sensor measurements.
Parameter 16-31 System Temp
. uses all elements in this array to calculate the system temperature.
Parameter 43-01 Auxiliary Temp.
Table 741: Parameter 43-01 Auxiliary Temp.
43-01 Auxiliary Temp.
Default Value: 0 °C
Parameter Type: Range, -128 - 127 °C, Array [18]
Setup: All set-ups
Conversion Index: 100
Data Type: Int8
Change during operation: True
Shows the temperature of an auxiliary component. The elements of the array reference the temperature measurements from the
NTC temperature sensors connected to hardware components in the drive. Refer to the Operating Guide for specifications of tem-
perature sensor placement.
AU373327181955en-000101 / 130R1208 | 345
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide