Parameter 30-05 Wobble Jump Frequency [%]
Table 698: Parameter 30-05 Wobble Jump Frequency [%]
30-05 Wobble Jump Frequency [%]
Default Value: 0%
Parameter Type: Range, 0 - 100 %
Setup: All set-ups
Conversion Index: 0
Data Type: Uint8
Change during operation: True
The jump frequency can also be expressed as a percentage of the center frequency. The function is the same as for
parameter 30-04
Wobble Jump Frequency [Hz]
.
Parameter 30-06 Wobble Jump Time
Table 699: Parameter 30-06 Wobble Jump Time
30-06 Wobble Jump Time
Default Value: Size related
Parameter Type: Range, 0.005 - 5.000 s
Setup: All set-ups
Conversion Index: -3
Data Type: Uint16
Change during operation: True
This parameter determines the slope of the jump ramp at the maximum and minimum wobble frequency.
Parameter 30-07 Wobble Sequence Time
Table 700: Parameter 30-07 Wobble Sequence Time
30-07 Wobble Sequence Time
Default Value: 10 s
Parameter Type: Range, 1 - 1000 s
Setup: All set-ups
Conversion Index: -1
Data Type: Uint16
Change during operation: True
This parameter determines the wobble sequence period. This parameter can only be changed in stop mode.
Wobble time =
t
up
+
t
down
Parameter 30-09 Wobble Random Function
Table 701: Parameter 30-09 Wobble Random Function
30-09 Wobble Random Function
Default Value: [0] Off
Parameter Type: Option
Setup: All set-ups
Conversion Index: -
Data Type: Uint8
Change during operation: True
Option
Name
Description
[0]*
Off
[1]
On
Parameter 30-10 Wobble Ratio
Table 702: Parameter 30-10 Wobble Ratio
30-10 Wobble Ratio
Default Value: 1
Parameter Type: Range, 0.1 - 10
Setup: All set-ups
Conversion Index: -1
Data Type: Uint8
Change during operation: True
If the ratio 0.1 is selected: t
down
is 10 times greater than t
up
. If the ratio 10 is selected: t
up
is 10 times greater than t
down
.
Center frequency
Use
parameter group 3-1* References
to set the center frequency.
AU373327181955en-000101 / 130R1208
336 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321