Option
Name
Description
[1]
LCP off
[1]
Internal fan off
[7]
Gatedrive off
[10]
Mains off
[13]
External fan off
[255]*
Ready to operate
Parameter 14-49 PROFIEnergy Info
Table 505: Parameter 14-49 PROFIEnergy Info
14-49 PROFIEnergy Info
Default value: 0
Parameter type: Range, 0 - 0x7ffffff, Array [115]
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
Read-out information about PROFIEnergy.
4.14.6 14-5* Environment
N O T I C E
Perform a power cycle after changing any of the parameters in this parameter group.
Use these parameters when operating the drive under special environmental conditions.
Parameter 14-50 RFI Filter
Table 506: Parameter 14-50 RFI Filter
14-50 RFI Filter
Default Value: [1] On
Parameter Type: Option
Setup: 1 set-up
Conversion Index: -
Data Type: Uint8
Change during operation: False
Turn the RFI filter on or off. The RFI filter ensures that the drive complies with EMC standards. Select
[0] Off
only when the drive is
connected to an isolated mains source (IT mains).
Option
Name
Description
[0]
Off
[1]*
On
Parameter 14-51 DC-link Compensation
Table 507: Parameter 14-51 DC-link Compensation
14-51 DC-link Compensation
Default Value: [1] On
Parameter Type: Option
Setup: All set-ups
Conversion Index: -
Data Type: Uint8
Change during operation: True
The rectified AC-DC voltage in the DC link of the drive is associated with voltage ripples. These ripples can increase in magnitude
with increased load. These ripples are undesirable because they can generate current and torque ripples. A compensation method
AU373327181955en-000101 / 130R1208 | 277
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide