Ex.
5 V
10 V
300
600
900
1200
1500
150
e3
0b
t1
03
.1
0
1 V
Par 6-xx
'Low Voltage'or
'Low Current'
Par 6-xx
'High Voltage'or
'High Current'
Analog input
Ref./Feedback
[RPM]
Par 6-xx
'High Ref./
Feedb. Value'
Par 6-xx
'Low Ref./
Feedb. Value'
Illustration 61: Analog Input 1
Parameter 6-10 Terminal 53 Low Voltage
Table 345: Parameter 6-10 Terminal 53 Low Voltage
6-10 Terminal 53 Low Voltage
Default value: Size related
Parameter type: Range, -10.00 - par. 6-11 V
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Enter the low voltage value. This analog input scaling value should correspond to the minimum reference value set in
parameter
6-14 Terminal 53 Low Ref./Feedb. Value
.
Parameter 6-11 Terminl 53 High Voltage
Table 346: Parameter 6-11 Terminal 53 High Voltage
6-11 Terminal 53 High Voltage
Default value: 10 V
Parameter type: Range, par. 6-11 V - 10 V
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Enter the high voltage value. This analog input scaling value should correspond to the high reference feedback value set in
parame-
ter 6-15 Terminal 53 High Ref./Feedb. Value
.
Parameter 6-12 Terminal 53 Low Current
Table 347: Parameter 6-12 Terminal 53 Low Current
6-12 Terminal 53 Low Current
Default value: 0.14 mA
Parameter type: Range, par. 0 - par. 6-13 mA
Setup: All setups
Conversion index: -5
Data type: Int16
Change during operation: True
Enter the low current value. This reference signal should correspond to the minimum reference value, set in
parameter 3-02 Mini-
mum Reference
. Set the value to exceed 2 mA to activate the live zero timeout function in
parameter 6-01 Live Zero Timeout Function
.
Parameter 6-13 Terminal 53 High Current
Table 348: Parameter 6-13 Terminal 53 High Current
6-13 Terminal 53 High Current
Default value: 20 mA
Parameter type: Range, par. par. 6-12 mA - 20 mA
Setup: All setups
Conversion index: -5
Data type: Int16
Change during operation: True
Enter the high current value corresponding to the high reference/feedback set in
parameter 6-15 Terminal 53 High Ref./Feedb. Value
.
AU373327181955en-000101 / 130R1208 | 181
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide