110
e3
0b
a2
60
.1
0
105
100
95
60s
100
90.7
98
Current
% of rated
Time
Desired current>100%
Inverter
load
counter
Time
Warning
Warning
~
~
Illustration 80: Output Current in Overload Condition
If the motor is unable to run continuously with the demanded capacity, run it at reduced speed for a while.
Select
parameter 14-61 Function at Inverter Overload
to automatically reduce motor speed until the output current is below 100% of
the rated current (set in
parameter 14-62 Inv. Overload Derate Current
).
Parameter 14-61 Function at Inverter Overload
is an alternative
to letting the drive trip.
The drive estimates the load on the power section with an inverter load counter, which causes a warning at 98% and a reset of the
warning at 90%. At the value 100%, the drive trips and issues an alarm. Status for the counter can be read in
parameter 16-35 Inverter
Thermal
.
If
parameter 14-61 Function at Inverter Overload
is set to
[3] Derate
, the motor speed is reduced when the counter exceeds 98%, and
stays reduced until the counter has dropped below 90.7%. If
parameter 14-62 Inv. Overload Derate Current
is set to for example 95%,
a steady overload causes the pump speed to fluctuate between values corresponding to 110% and 95% of rated output current for
the drive.
Parameter 14-61 Function at Inverter Overload
Table 515: Parameter 14-61 Function at Inverter Overload
14-61 Function at Inverter Overload
Default Value: [0] Trip
Parameter Type: Option
Setup: All set-ups
Conversion Index: -
Data Type: Uint8
Change during operation: True
Use if there is a steady overload beyond the thermal limits (110% for 60 s).
Option
Name
Description
[0]*
Trip
Select
[0] Trip
to make the drive trip and issue an alarm.
[1]
Derate
Reduces the motor speed to decrease the load on the power section and allowing it to cool down.
Parameter 14-62 Inv. Overload Derate Current
Table 516: Parameter 14-62 Inv. Overload Derate Current
14-62 Inv. Overload Derate Current
Default Value: 95%
Parameter Type: Range, 50 - 100%
Setup: All set-ups
Conversion Index: 0
Data Type: Uint16
Change during operation: True
Enter the current level (in % of rated output current for the drive) when running with reduced motor speed after load on the drive
has exceeded the allowable limit (110% for 60 s).
AU373327181955en-000101 / 130R1208 | 281
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide