•
•
•
•
•
•
•
Parameter 3-02 Minimum Reference
Set the minimum speed of the
motor shaft.
Parameter 3-03 Maximum Reference
Set the maximum speed of the
motor shaft.
Parameter 3-41 Ramp 1 Ramp Up Time
Set the ramp-up time with refer-
ence to synchronous motor
speed, n
s
.
Parameter 3-42 Ramp 1 Ramp Down
Time
Set the ramp-down time with ref-
erence to synchronous motor
speed, n
s
.
Parameter 3-13 Reference Site
Set the site from where the refer-
ence must work.
Another easy way of commissioning the drive is by using the smart application set-up (SAS), which can also be found by pressing
[Quick Menu]. To set up the applications listed, follow the instructions on the successive screens.
The [Info] key can be used throughout the SAS to see help information for various selections, settings, and messages. The following
3 applications are included:
Mechanical brake.
Conveyor.
Pump/fan.
The following 4 fieldbusses can be selected:
PROFIBUS.
PROFINET.
DeviceNet.
EtherNet/IP.
N O T I C E
The drive ignores the start conditions when SAS is active.
N O T I C E
The smart set-up runs automatically on the first power-up of the drive or after a reset to factory settings. If no action is taken, the
SAS screen automatically disappears after 10 minutes.
AU373327181955en-000101 / 130R1208
28 | Danfoss A/S © 2021.08
How to Program
VLT® AutomationDrive EZ FC 321
Programming Guide