N O T I C E
The drive has no back-up of the clock function. The set date/time is reset to default (2000-01-01 00:00) after a power-down. In
parameter 0-79 Clock Fault
, it is possible to program a warning if the clock has not been set properly, for example after a power-
down. Set the time at least 1 hour later than actual time.
Parameter 23-15 Reset Maintenance Word
Table 690: Parameter 23-15 Reset Maintenance Word
23-15 Reset Maintenance Word
Default Value: [0] Do not reset
Parameter Type: Option
Setup: All set-ups
Conversion Index: -
Data Type: Uint8
Change during operation: True
N O T I C E
When messages are reset, maintenance item, action, and maintenance date/time are not canceled.
Parameter 23-12 Maintenance
Time Base
is set to
[0] Disabled
.
Set this parameter to
[1] Do reset
to reset the maintenance word in
parameter 16-96 Maintenance Word
and reset the message shown
in the LCP. This parameter changes back to
[0] Do not reset
when pressing [OK].
Option
Name
Description
[0]*
Do not reset
[1]
Do reset
Parameter 23-16 Maintenance Text
Table 691: Parameter 23-16 Maintenance Text
23-16 Maintenance Text
Default Value: 0
Parameter Type: Range, 0 - 20, Array [6]
Setup: 1 set-up
Conversion Index: 0
Data Type: VisStr[20]
Change during operation: True
6 individual texts (Maintenance Text 0...Maintenance Text 5) can be written for use in either
parameter 23-10 Maintenance Item
or
parameter 23-11 Maintenance Action
. The text is written according to the guidelines in
parameter 0-37 Display Text 1
.
Parameter 23-18 Reset Mechanical Brake Counter
Table 692: Parameter 23-18 Reset Mechanical Brake Counter
23-18 Reset Mechanical Brake Counter
Default Value: [0] Do not reset
Parameter Type: Option
Setup: All set-ups
Conversion Index: -
Data Type: Uint8
Change during operation: True
Option Name
Description
[0]*
Do not reset Select this option to disable the reset of the mechanical brake counter.
[1]
Do reset
Select this option to enable the reset of the mechanical brake counter. After resetting the mechanical
brake counter, the parameter is set to
[0] Do not reset
, which is the default option.
AU373327181955en-000101 / 130R1208 | 333
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide