Option
Name
Description
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
Example
Use multi set-up to shift from setup 1 to setup 2 while the motor is running. Program in setup 1 first, then ensure that setup 1 and
setup 2 are synchronized (or linked). Synchronization can be performed in 2 ways:
Select the following options:
[2] Set-up 2
in
parameter 0-11 Edit Set-up
Set
parameter 0-12 This Set-up Linked to
to
[1] Set-up 1
.
e
7
5
b
p
0
7
5
.1
1
Illustration 24: Set-up 1
While still in setup 1, copy setup 1 to setup 2. Then set
parameter 0-12 This Set-up Linked to
to
[2] Set-up 2
.
e
3
0
b
p
0
7
6
.1
1
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[2]
Setup 2
Illustration 25: Setup 2
Parameter 0-13 Readout: Linked Set-ups
Table 16: Parameter 0-13 Readout: Linked Set-ups
0-13 Readout: Linked Set-ups
Default value: 0
Parameter type: Range [0–255]
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: False
View a list of all the setups linked by
parameter 0-12 This Set-up Linked to
. The parameter has 1 index for each parameter setup. The
value for each index shows which setups are linked to that parameter setup.
AU373327181955en-000101 / 130R1208
36 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide