The Cos(phi) setpoint is automatically set for optimum AEO performance. This parameter should normally not be altered. However,
in some situations it may be necessary to enter a new value to fine-tune.
Parameter 14-44 d-axis Reference Gain
Table 501: Parameter 14-44 d-axis Reference Gain
14-44 d-axis Reference Gain
Default value: 100%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: True
Adjustment parameter for the d-axis current. 100% indicates maximum torque per ampere value based on motor parameters. In-
creasing the maximum torque can improve the power factor of the machine which may increase the current consumption. The
adjustment parameter allows to:
Adjust minimum current consumption, allowing for tolerances in the motor parameters.
Obtain the optimal balance between current consumption and power factor of the machine at a given point of operation.
Parameter 14-46 PROFIEnergy Times
Table 502: Parameter 14-46 PROFIEnergy Times
14-46 PROFIEnergy Times
Default value: Size related
Parameter type: Range, 0 - 0x7ffffff, Array [3]
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
Parameter with an array of 3.
[0] Time to pause
,
[1] Time min stay
,
[2] Time regular operate
.
Parameter 14-47 PROFIEnergy State
Table 503: Parameter 14-47 PROFIEnergy State
14-47 PROFIEnergy State
Default Value: [255] Ready to operate
Parameter Type: Option
Setup: 2 set-ups
Conversion Index: -
Data Type: Uint8
Change during operation: False
Option
Name
Description
[1]
LCP off
[1]
Internal fan off
[7]
Gatedrive off
[10]
Mains off
[13]
External fan off
[255]*
Ready to operate
Parameter 14-48 PROFIEnergy Desired State
Table 504: Parameter 14-48 PROFIEnergy Desired State
14-48 PROFIEnergy Desired State
Default Value: [255] Ready to operate
Parameter Type: Option
Setup: 2 set-ups
Conversion Index: -
Data Type: Uint8
Change during operation: False
AU373327181955en-000101 / 130R1208
276 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide