Option Name
Description
[17]
Analog input AICCT
Value is in [°]. AICCT us control card temperature.
[18]
Pulse input FI29
The value is in %.
[19]
Pulse input FI33
The value is in %.
[20]
Alarm number
The number or registered alarms
[21]
Warning number
[22]
Analog input X30/11
[23]
Analog input X30/12
[30]
Counter A
[31]
Counter B
[32]
Process PID error
Value of the PID error (
parameter 18-90 Process PID Error
).
[33]
Process PID Output
Value of the PID output (
parameter 18-91 Process PID Output
).
[34]
Analog input X48/2
[35]
Temp input X48/4
[36]
Temp input X48/7
[37]
Temp input X48/10
[39]
Safe opt. speed error
[43]
Analog input X49/3
[45]
Analog input X49/5
[50]
FALSE
Use to enter the fixed value
False
in the comparator.
[51]
TRUE
Use to enter
True
in the comparator.
[52]
Control ready
The control board receives supply voltage.
[53]
Drive ready
The drive is ready for operation and applies a signal on the control board.
[54]
Running
The motor runs.
[55]
Reversing
The output is active when the drive runs counterclockwise (the logical product of the status
bits running AND reverse).
[56]
In range
The motor runs within the programmed current and speed ranges set in
parameter 4-50 Warn-
ing Current Low
to
parameter 4-53 Warning Speed High
.
[60]
On reference
The motor runs on reference.
[61]
Below reference, low
The motor runs at a reference which is less than the value in
parameter 4-54 Warning Reference
Low
.
[62]
Above ref, high
The motor runs at a reference which exceeds the value in
parameter 4-55 Warning Reference
High
.
[65]
Torque limit
The torque exceeds the value in
parameter 4-16 Torque Limit Motor Mode
or
parameter 4-17 Tor-
que Limit Generator Mode
.
AU373327181955en-000101 / 130R1208