Parameter 1-00 Configuration Mode
Table 60: Parameter 1-00 Configuration Mode
1-00 Configuration Mode
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the application control principle to be used when a remote reference (that is via analog input or fieldbus) is active. A remote
reference can only be active when
parameter 3-13 Reference Site
is set to
[0] Linked to Hand/Auto
or
[1] Remote
.
Op-
tion
Name
Description
[0]
Speed open
loop
Enables speed control (without feedback signal from motor) with automatic slip compensation for al-
most constant speed at varying loads. Compensations are active, but can be disabled in
parameter
group 1-** Load and Motor
. Set the speed control parameters in
parameter group 7-0* Speed PID Ctrl
.
[1]
Speed closed
loop
Enables speed closed-loop control with feedback. Obtain full holding torque at 0 RPM. For increased
speed accuracy, provide a feedback signal and set the speed PID control. Set the speed control param-
eters in
parameter group 7-0* Speed PID Ctrl
.
[2]
Torque
Enables torque closed-loop control with feedback. Only possible when
parameter 1-01 Motor Control
Principle
is set to
[3] Flux w/motor feedb
.
[3]
Process
Enables the use of process control in the drive. Set the process control parameters in
parameter groups
7-2* Process Ctrl. Feedb.
and
7-3* Process PID Ctrl
.
[4]
Torque open
loop
Enables the use of torque open-loop mode (
parameter 1-01 Motor Control Principle
). Set the torque PID
parameters in
parameter group 7-1* Torque PI Control
.
[5]
Wobble
Enables the wobble functionality in
parameter 30-00 Wobble Mode
to
parameter 30-19 Wobble Delta
Freq. Scaled
.
[6]
Surface wind-
er
Enables the surface winder control-specific parameters in
parameter groups 7-2* Process Ctrl. Feedb.
and
7-3* Process PID Ctrl.
[7]
Extended PID
speed OL
Specific parameters in
parameter groups 7-2* Process Ctrl. Feedb.
to
7-5* Ext. Process PID Ctrl.
[8]
Extended PID
speed CL
Specific parameters in
parameter groups 7-2* Process Ctrl. Feedb.
to
7-5* Ext. Process PID Ctrl.
Parameter 1-01 Motor Control Principle
Table 61: Parameter 1-01 Motor Control Principle
1-01 Motor Control Principle
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: False
Select which motor control principle to employ.
AU373327181955en-000101 / 130R1208 | 57
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide