Parameter 6-53 Term 42 Output Bus Ctrl
Table 362: Parameter 6-53 Term 42 Output Bus Ctrl
6-53 Term 42 Output Bus Ctrl
Default value: 0%
Parameter type: Range, 0 - 100%
Setup: All setups
Conversion index: -2
Data type: N2
Change during operation: True
Holds the level of output 42 if controlled by bus.
Parameter 6-54 Term 42 Output Timeout Preset
Table 363: Parameter 6-54 Term 42 Output Timeout Preset
6-54 Term 42 Output Timeout Preset
Default value: 0%
Parameter type: Range, 0 - 100%
Setup: 1 setup
Conversion index: -2
Data type: Uint16
Change during operation: True
Holds the preset level of output 42. If a timeout function is selected in
parameter 6-50 Terminal 42 Output
, the output is preset to this
level if a fieldbus timeout occurs.
Parameter 6-55 Analog Output Filter
Table 364: Parameter 6-55 Analog Output Filter
6-55 Analog Output Filter
Default value: [0] Off
Parameter type: Option
Setup: 1 setup
Conversion index: –
Data type: Uint8
Change during operation: True
The following readout parameters from selection in
parameter 6-50 Terminal 42 Output
have a filter selected when
parameter 6-55
Analog Output Filter
is on:
Table 365: Readout Parameters
Selection
0–20 mA
4–20 mA
Motor current (I
max
)
[103]
[133]
Torque limit (0–T
lim
)
[104]
[134]
AU373327181955en-000101 / 130R1208 | 187
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide