The delta frequency determines the magnitude of the wobble frequency. The delta frequency is superimposed on the center fre-
quency.
Parameter 30-01 Wobble Delta Frequency [Hz]
contains both the positive and negative delta frequency. The setting of
param-
eter 30-01 Wobble Delta Frequency [Hz]
must thus not exceed the setting of the center frequency. The initial ramp-up time from
standstill until the wobble sequence runs is determined in
parameter group 3-1* References
.
Parameter 30-02 Wobble Delta Freqeuncy [%]
Table 695: Parameter 30-02 Wobble Delta Freqeuncy [%]
30-02 Wobble Delta Freqeuncy [%]
Default Value: 25%
Parameter Type: Range, 0 - 100%
Setup: All set-ups
Conversion Index: 0
Data Type: Uint8
Change during operation: True
The delta frequency can also be expressed as a percentage of the center frequency and can thus be maximum 100%. The function is
the same as for
parameter 30-01 Wobble Delta Frequency [Hz]
.
Parameter 30-03 Wobble Delta Freq. Scaling Resource
Table 696: Parameter 30-03 Wobble Delta Freq. Scaling Resource
30-03 Wobble Delta Freq. Scaling Resource
Default Value: [0] No function
Parameter Type: Option
Setup: All set-ups
Conversion Index: -
Data Type: Uint8
Change during operation: True
Select the drive input to be used for scaling the delta frequency setting.
Option
Name
Description
[0]*
No function
[1]
Analog input 53
[2]
Analog input 54
[3]
Frequency input 29
[4]
Frequency input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[15]
Analog input X48/2
[16]
Analog input X49/1
[17]
Analog input X49/3
[18]
Analog input X49/5
Parameter 30-04 Wobble Jump Frequency [Hz]
Table 697: Parameter 30-04 Wobble Jump Frequency [Hz]
30-04 Wobble Jump Frequency [Hz]
Default Value: 0 Hz
Parameter Type: Range, 0 - 20.0 Hz
Setup: All set-ups
Conversion Index: -1
Data Type: Uint8
Change during operation: True
The jump frequency is used to compensate for the inertia in the traverse system. If a jump in the output frequency is required at the
boundaries of the wobble sequence, the frequency jump is set in this parameter. If the traverse system has a very high inertia, a high
jump frequency may create a torque limit warning or trip or an overvoltage warning or trip. This parameter can only be changed in
stop mode.
AU373327181955en-000101 / 130R1208 | 335
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide