Option
Name
Description
[103]
Motor current
[104]
Torque rel to limit
[105]
Torque related to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max out freq
[119]
Torque % lim
Parameter 5-65 Pulse Output Max Freq #29
Table 331: Parameter 5-65 Pulse Output Max Freq #29
5-65 Pulse Output Max Freq #29
Default value: Size related
Parameter type: Range, 0 - 32000 Hz
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
Set the maximum frequency for terminal 29 corresponding to the output variable selected in
parameter 5-63 Terminal 29 Pulse Out-
put Variable
.
4.6.7 5-7* 24 V Encoder Input
Connect the 24 V encoder to terminal 12 (24 V DC supply), terminal 32 (channel A), terminal 33 (channel B), and terminal 20 (GND).
The digital inputs 32/33 are active for encoder inputs when
[1] 24 V encoder
is selected in
parameter 1-02 Flux Motor Feedback Source
and
parameter 7-00 Speed PID Feedback Source
. The encoder used is a dual-channel (A and B) 24 V type. Maximum input frequency:
110 kHz.
Encoder connection to the drive
24 V incremental encoder. Maximum cable length is 5 m (16.4 ft).
AU373327181955en-000101 / 130R1208 | 175
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide