Parameter 6-00 Live Zero Timeout Time
Table 343: Parameter 6-00 Live Zero Timeout Time
6-00 Live Zero Timeout Time
Default value: 10 s
Parameter type: Range, 0 - 99 s
Setup: All setup
Conversion index: 0
Data type: Int16
Change during operation: True
Enter the live zero timeout in s. Live zero timeout time is active for analog inputs, that is terminal 53 or terminal 54, used as refer-
ence or feedback sources. If the reference signal value associated with the selected current input drops below 50% of the value set
in:
Parameter 6-10 Terminal 53 Low Voltage
Parameter 6-12 Terminal 53 Low Current
Parameter 6-20 Terminal 54 Low Voltage
Parameter 6-22 Terminal 54 Low Current
for a time period longer than the time set in
parameter 6-00 Live Zero Timeout Time
, the function selected in
parameter 6-01 Live Zero
Timeout Function
is activated.
Parameter 6-01 Live Zero Timeout Function
Table 344: Parameter 6-01 Live Zero Timeout Function
6-01 Live Zero Timeout Function
Default value: [0] Off
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the timeout function. If the input signal on terminal 53 or 54 is below 50% of the value in
Parameter 6-10 Terminal 53 Low Voltage
Parameter 6-12 Terminal 53 Low Current
Parameter 6-20 Terminal 54 Low Voltage
Parameter 6-22 Terminal 54 Low Current
for a time period defined in
parameter 6-00 Live Zero Timeout Time
, then the function set in
parameter 6-01 Live Zero Timeout Function
is activated. If several timeouts occur simultaneously, the drive prioritizes the timeout functions as follows:
Parameter 6-01 Live Zero Timeout Function
Parameter 8-04 Control Word Timeout Function
Option
Name
Description
[0]*
Off
[1]
Freeze output
Frozen at the present value.
[2]
Stop
Overruled to stop.
[3]
Jogging
Overruled to jog speed.
[4]
Max. speed
Overruled to maximum speed.
[5]
Stop and trip
Overruled to stop with subsequent trip.
[20]
Coast
[21]
Coast and trip
4.7.2 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog input 1 (terminal 53).
AU373327181955en-000101 / 130R1208
180 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide