Parameter 8-83 Slave Error Count
Table 450: Parameter 8-83 Slave Error Count
8-83 Slave Error Count
Default value: 0
Parameter type: Range, 0 - 0
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
This parameter shows the number of error telegrams which are not executed by the drive.
4.10 Parameter Group 9-** PROFIBUS
For PROFIBUS parameter descriptions, see the VLT® PROFIBUS DP MCA 101 Programming Guide.
4.11 Parameter Group 10-** CAN Fieldbus
For DeviceNet parameter descriptions, see the VLT® DeviceNet MCA 104 Programming Guide.
4.12 Parameter Group 12-** Ethernet
For Ethernet parameter descriptions, see the VLT® EtherNet/IP MCA 121 Programming Guide.
4.13 Parameter Group 13-** Smart Logic Control
Smart logic control (SLC) is a sequence of user-defined actions (see
parameter 13-52 SL Controller 1 Action
) executed by the SLC when
the associated user-defined event (see
parameter 13-51 SL Controller 1 Event
) is evaluated as true by the SLC. The condition for an
event can be a particular status, or that the output from a logic rule or a comparator operand becomes true. That leads to an associ-
ated action as illustrated:
. . .
. . .
Par. 13-11
Comparator Operator
Par. 13-43
Logic Rule Operator 2
Par. 13-51
SL Controller Event
Par. 13-52
SL Controller Action
e3
0b
b6
71
.1
3
Coast
Start timer
Set Do X low
Select set-up 2
. . .
Running
Warning
Torque limit
Digital input X 30/2
. . .
=
TRUE longer than..
. . .
. . .
Illustration 68: Smart Logic Control (SLC)
Events and actions are each numbered and linked in pairs (states). This means that when the 1
st
event is fulfilled (becomes true), the
1
st
action is executed. After this, the conditions of the 2
nd
event are evaluated and if evaluated true, the 2
nd
action is executed, and
so on. Only 1 event is evaluated at any time. If an event is evaluated as false, nothing happens (in the SLC) during the current scan
interval and no other events are evaluated. This means that when the SLC starts, it evaluates the 1
st
event (and only the 1
st
event) in
each scan interval. Only when the 1
st
event is evaluated as true, the SLC executes the 1
st
action and starts evaluating the 2
nd
event.
It is possible to program 1–20 events and actions. When the last event/action has been executed, the sequence starts over again
from the 1
st
event/action.
AU373327181955en-000101 / 130R1208
228 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide