Selected
event
Relay
output
On delay
P 5-41
Off delay
P 5-42
e3
0b
a1
72
.1
1
Illustration 56: Off Delay, Relay
If the selected event condition changes before the on delay or off delay timer expires, the relay output is unaffected.
4.6.5 5-5* Pulse Input
The pulse input parameters are used to define an appropriate window for the impulse reference area by configuring the scaling and
filter settings for the pulse inputs. Input terminals 29 or 33 act as frequency reference inputs. Set terminal 29 (
parameter 5-13 Termi-
nal 29 Digital Input
) or terminal 33 (
parameter 5-15 Terminal 33 Digital Input
) to
[32] Pulse input
. If terminal 29 is used as an input, set
parameter 5-01 Terminal 27 Mode
to
[0] Input
.
e3
0b
a0
76
.1
1
(RPM)
Ref.
Low freq.
P 5-50/
P 5-55
Input
(Hz)
High
ref.
value
P 5-53/
p 5-58
High freq.
P 5-51/
P 5-56
Low
ref.
value
P 5-52/
p 5-57
Illustration 57: Pulse Input
Parameter 5-50 Term. 29 Low Frequency
Table 317: Parameter 5-50 Term. 29 Low Frequency
5-50 Term. 29 Low Frequency
Default value: 100 Hz
Parameter type: Range, 0 – 110000 Hz
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
Enter the low frequency limit corresponding to the low motor shaft speed (that is low reference value) in
parameter 5-52 Term. 29
Low Ref./Feedb. Value
.
Parameter 5-51 Term. 29 High Frequency
Table 318: Parameter 5-51 Term. 29 High Frequency
5-51 Term. 29 High Frequency
Default value: Size related
Parameter type: Range, 0 – 110000 Hz
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
Enter the high frequency limit corresponding to the high motor shaft speed (that is high reference value) in
parameter 5-53 Term. 29
High Ref./Feedb. Value
.
AU373327181955en-000101 / 130R1208
170 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide