i-on Range
Installer Menu Options
Page 45
Log Only – LO (17)
When a detector triggers a zone with this type the control unit logs the
event and activates any outputs that are programmed to follow this zone.
The zone is active whether the system is set or unset. Typical uses for this
zone type are for integrating the alarm system with a CCTV system.
Note: Zone Follow outputs will activate on both Alarm and Tamper of a Log
Only zone.
Exit Terminate ET (18)
Use this zone type to terminate setting when the system or partition exit
mode is ―Exit Terminate‖ (see page 71). This zone type is designed for a
normally open momentary switch. Note that this zone type is armed
during the setting time, but inactive both while the system is set, and
while the system is unset. If you apply the Chime attribute to this zone,
then the system will give a chime tone when the zone is activated both
while the system is unset and while the system is set.
Note: Zone types 19 and 20 are not used.
Lock Set LS (21)
Use this zone type to complete setting when the system or partition exit
mode is ―Lock Set‖ (see page 72). This zone type is designed for a
normally open switch. Note that
this zone type is monitored by the panel
only when the system or partition is arming or armed
.
A Lock Set zone can take the Inverted attribute.
Note: Zone types 22 and 23 are not used.
Tamper Return TR (24)
30 40 50 160
Assign this zone type to the connection point used for wiring a tamper
return wire from an external sounder (see the relevant control unit‘s
Installation Guide for details).
The control unit monitors a Tamper Return zone at all times. When
triggered in the unset condition, only internal sounders operate. When
triggered in the set condition, the alarm response determines whether
external sounders, strobe and communications also respond to the alarm.
You can assign the Soak Test, Part Set, Omitable and Force Set attribute
to this zone type.
Note that the type of zone wiring assigned to the connection point determines
the length of tamper return cable. For a single core of standard alarm cable:
CC wiring has a limit of 6m
FSL 2k2/4k7 or 4k7/4k7 will allow up to 50m. (Cooper Security
recommend that you do not use any other resistor pair values.)
Partitions
30 40 50 160
Note: This menu does not appear if a zone has the type “Not Used”.