i-on160
Appendix I
Page 193
SIA3:
#AAAAAA|Ntihh:mm/idnnn/rinn/CCcc
#AAAAAA|AS
Extended
SIA 3:
#AAAAAA|Ntihh:mm/idnnn/rinn/CCcc/AS
Where:
AAAAAA
6-digit programmable account code (e.g. 123456).
―N‖
New Event (always N).
―ti‖hh:mm/
time (e.g. ti10:23/).
―id‖nnn/
user number, if applicable; otherwise not sent (e.g.
id123/ or id6/).
―ri‖nn/
partition no. (e.g. ri12/ or ri3).
CC
event code (e.g. FA = Fire Alarm).
cc
zone or keypad number, if applicable; otherwise
not sent (e.g. 23 or 5).
―A‖S
text description of event, usually the log event
description.
(The control unit sends those characters shown between ― and ― above literally
as they appear in the text.)
For example, if there is a fire alarm on zone 2 of partition 4 at 10:15 (partition
4 account number is 10), the message would be:
SIA1:
#000010|NFA2
SIA2:
#000010|N/ri4/FA2
SIA3:
#000010|Nti10:15/ri4/FA2 #000010|AFire
Zone 2
Extended SIA3:
#000010|Nti10:15/ri4/FA2/AFire Zone 2