Installer Menu Options
i-on Range
Page 44
External PSU A/C Fail – PAC (11)
30 40 50 160
Use this zone type to monitor the A/C Fail output of an external power
supply unit. If a power supply unit triggers a zone with this type then the
control unit responds by: logging a Mains Fail, activating any output
programmed as ―A/C Fail‖, starting any programmed communication, and
causing an alert that displays ―External mains fail‖ on the keypad(s).
However, the timing of the response varies as follows:
While the system is
unset
:
a) If EITHER mains is present at the control unit OR has been absent at
the control unit for more than 10s then the control unit responds
immediately.
b) If mains fails at the control unit at the same time as the external PSU
triggers the zone input (+/- 10s) then the control unit waits for the time
programmed in
System Options – Mains Fail Delay
(see page 95). If control
unit mains is still absent at the end of that time then the control unit
responds as described above.
While the alarm system is
set
then the timing of the control unit‘s
response is the same as described in a) or b) above, but the control unit
hides the keypad alert until the system is unset.
External PSU Battery Fault - PBF (12)
30 40 50 160
Use this zone type to monitor the Battery Fault output of an external
power supply unit. If an external PSU triggers a zone with this type then
the control unit activates any output programmed as ―Battery Fault‖ and
causes an alert that displays ―External Battery Fault‖ on the keypad.
If the alarm system is set then the control unit logs the event, starts any
programmed communication, but does not start an alert until the system
is unset.
External PSU Low Volts – PLV (13)
30 40 50 160
Use this zone type to monitor the Low Voltage output of an external power
supply unit. If a power supply triggers a zone with this type then the
control unit activates any output programmed as ―Low Volts‖ and causes
an alert that displays ―External Low Volts‖ on the keypad.
If the alarm system is set then the control unit logs the event, starts any
programmed communication, but does not start an alert until the system
is unset.
External PSU Fault – PF (14)
30 40 50 160
Use this zone type to monitor the fault output of an external PSU. (This
zone type is available for power supplies that do not provide specific fault
outputs that can be used by zone types 11, 12 and 13.) If a power supply
triggers a zone with this type then the control unit activates any output
programmed as ―External PSU Fault‖ and causes an alert that displays
―External power fault‖ on the keypad.
If the alarm system is set then the control unit logs the event, starts any
programmed communication, but does not start an alert until the system
is unset.
Note: Zone types 15 and 16 are not used.