Installer Menu Options
i-on Range
Page 66
Type:
(nn=shortcut)
Active when:
Assign to
Partitions?
Shock Sensor
Reset (26)
30 40 50
160
Exit time starts. The output remains active
for five seconds. Use this output to reset
shock sensors (for example, the "Viper").
Yes
Walk Test (27)
A user starts Installer- or User Walk Tests.
Also active during the time between
silencing and resetting the system. This
output can be used on movement
detectors that are able to switch off the
Walk Test lamp in any state other than a
Walk Test.
No
Smoke Sensor
Reset (28)
30 40 50
160
This output is active (0V) all the time
except when a user acknowledges a fire
alarm: after which the control unit
deactivates the output for three seconds.
This output type is designed to be
connected to low-voltage smoke detector
reset terminals.
Yes
24 Hour Alarm
(29)
The control unit starts a 24 hour alarm.
Yes
Setting
Complete (30)
The control unit finishes setting. Active for
10 seconds.
Yes
Unset Complete
(31)
Someone unsets the system or disarms it
after an alarm. The output is active for 10
seconds.
Yes
Full Set Ready
(32)
None of the detectors are reporting ―alarm‖
signals.
Yes (all
partitions by
default)
Full Set (33)
The system is full set. If the system is
partitioned, then the output is active only
when all assigned partitions are Full Set.
Yes
Part Set (34)
The system is part set.
Yes
Part Set B (35)
Setting Part Set B. Deactivated on
unsetting Part Set B. (Available only in a
Part Setting system)
No
Part Set C (36)
Setting Part Set C. Deactivated on
unsetting Part Set C. (Available only in a
Part Setting system)
No
Part Set D (37)
Setting Part Set D. Deactivated on
unsetting Part Set D. (Available only in a
Part Setting system)
No
Set Fail (38)
A set command fails. Remains active until
the user acknowledges the set fail.
Yes