8A
la
rm
DX100
8.3
A
la
rm Me
ssa
ge List
8-423
Module
failure(converter)
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the SERVOPACK.
EAXA board failure
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the EAXA board. Save the CMOS.BIN
before replacing the board to be safe.
4340
TEMPERATURE
ERROR(CONVER
TER)
Sub Code: Signifies the physical
No. of converter in which the alarm
occurred
Voltage failure
Modify the primary breaker voltage to the specified voltage 200V(+10% to
15%).
Connection failure
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, check the connection and inserting state of the
following cables and connectors.
·EAXA01-CN507,510
·EAXB01-CN08
·Converter CN551,553
Module
failure(converter)
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the SERVOPACK.
EAXA board failure
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the EAXA board. Save the CMOS.BIN
before replacing the board to be safe.
High ambient
temperature
Adjust the ambient temperature to 40C°C° or less.
Install failure
Check that the air inlet or outlet is not blocked.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy