Connection failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, check the connection and insertion of the
following connector.
· The PCI connector of the TOYOPUC board
22
An error was found in the specified
number of registers which are
used by the system data "INST.
MESSAGE" of allocation
configuration.
Setting error
(1)Check the following settings.
· Allocation configuration for the TOYOPUC
Connection failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, check the connection and insertion of the
following connector.
· The PCI connector of the TOYOPUC board
23
An error was found in the specified
number of registers for "Alarm/
Error/Message" in the system data
of Allocation setting information.
Setting error
(1)Check the following settings.
· Allocation configuration for the TOYOPUC
Connection failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, check the connection and insertion of the
following connector.
· The PCI connector of the TOYOPUC board
30
In the input side setting of
allocation configuration data, the
specified R-register start No. for
the TOYOPUC exceeds the R-
register limit.
Setting error
(1)Check the following settings.
· Allocation configuration for the TOYOPUC
Connection failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, check the connection and insertion of the
following connector.
· The PCI connector of the TOYOPUC board
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy