8A
la
rm
DX100
8.3
A
la
rm Me
ssa
ge List
8-290
4110
SHOCK SENSOR
ACTION
Connection failure
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, check the connection and inserting state of the
following cables and connectors.
·YPU unit
·EAXA board CN512
YPU unit board
failure
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the YPU unit. Save the CMOS.BIN
before replacing the board to be safe.
EAXA board failure
(1)Reset the alarm.(In case of major alarm, turn the power OFF then back
ON.)
(2)If the alarm occurs again, replace the EAXA board. Save the CMOS.BIN
before replacing the board to be safe.
4112
DATA SENDING
ERROR
1
Retry over of NAK
Communication
error
(1)Reset the alarm.
(2)If the alarm occurs again, check the communication setting and
communication wiring is correct.
2
Retry over for timeout in timer A
Communication
error
(1)Reset the alarm.
(2)If the alarm occurs again, check the communication setting and
communication wiring is correct.
3
Retry over for mutual response
error
Communication
error
(1)Reset the alarm.
(2)If the alarm occurs again, check the communication setting and
communication wiring is correct.
4113
DATA RECEIVING
ERROR
1
Reception timeout (timer A)
Communication
error
(1)Reset the alarm.
(2)If the alarm occurs again, check the communication setting and
communication wiring is correct.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy