8A
la
rm
DX100
8.3
A
la
rm Me
ssa
ge List
8-36
Connection failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, check the connection and insertion of the
following connector.
· The PCI connector of the corresponding I/O module
Board failure(I/O
module)
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the following board. Save the
CMOS.BIN before replace the board to be safe.
· The corresponding I/O module (PCI board)
YIF board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YIF01 board. Save the CMOS.BIN
before replace the board to be safe. Replace the YIF01 board, and then load
the CMOS.BIN saved before alarm occurred.
0100
COMMUNICATION
ERROR(EAXA#1)
1
The error was detected during the
check of the serial communication
watchdog data.
Counter value received from EAXA
board is invalid.
Setting error
(1)Check the following settings.
· Control group settings in maintenance mode
· The EAXA board rotary switch setting (0) of the corresponding node
number (SV#1)
Connection failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, check the connection and insertion of the
following cables and connectors.
· The cable of EAXA board CN509
· The cable of EAXA board connector CN515/516
· The PCI connector of the YIF01 board
· The cable of YIF board connector CN113
EAXA board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA board. Save the CMOS.BIN
before replace the board to be safe.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy