Check first when you have troubles
Troubleshooting
7 - 26
7.6.5
Motor rotates in opposite direction
7.6.6
Speed greatly differs from the setting
7.6.7
Acceleration/deceleration is not smooth
Check Points
Possible Cause
Countermeasures
Refer to
Page
Main circuit
Phase sequence of output terminals U, V and
W is incorrect.
Connect phase sequence of the output
cables (terminal U, V, W) to the motor cor-
rectly
Input signal
The start signals (forward rotation, reverse
rotation) are connected improperly.
Check the wiring. (STF: forward rotation, STR:
reverse rotation)
Adjustment by the output frequency is
improper during the reversible operation
with Pr. 73 "Analog input selection" setting.
Check the setting of Pr. 125, Pr. 126, C2 to C7.
Parameter
setting
Pr. 40 "RUN key rotation direction selection"
setting is incorrect.
Check the Pr. 40 setting.
Check Points
Possible Cause
Countermeasures
Refer to
Page
Input signal
Frequency setting signal is incorrectly input.
Measure the input signal level.
—
The input signal lines are affected by external
EMI.
Take countermeasures against EMI such as
using shielded wires for input signal lines.
Parameter
setting
Pr. 1, Pr. 2, Pr. 18, calibration parameter C2 to
C7 settings are improper.
Check the settings of Pr. 1 "Maximum fre-
quency", Pr. 2 "Minimum frequency", Pr. 18
"High speed maximum frequency".
Check the calibration parameter C2 to C7 set-
tings.
Pr. 31 to Pr. 36 "Frequency jump" settings are
improper.
Narrow down the range of frequency jump.
Load
Stall prevention is activated due to a heavy
load.
Reduce the load weight.
—
Parameter
setting
Set Pr. 22 "Stall prevention operation level
"higher according to the load. (Setting Pr. 22
too large may result in frequent overcurrent
trip (E.OC
첸
).)
Motor
Check the capacities of the inverter and the
motor.
—
Check Points
Possible Cause
Countermeasures
Refer to
Page
Parameter
setting
Acceleration/deceleration time is too short.
Increase acceleration/deceleration time.
Torque boost (Pr. 0, Pr. 46) setting is improper
under V/F control, so the stall prevention
function is activated.
Increase/decrease Pr. 0 "Torque boost" set-
ting value by 0.5% increments to the setting.
The base frequency does not match the
motor characteristics.
For V/F control, set Pr. 3 "Base frequency" and
Pr. 47 "Second V/F (base frequency)".
For Advanced magnetic flux vector control or
General-purpose magnetic flux vector con-
trol, set Pr. 84 "Rated motor frequency".
Stall prevention function is activated due to a
heavy load.
Reduce the load weight.
—
Set Pr. 22 "Stall prevention operation level
"higher according to the load. (Setting Pr. 22
too large may result in frequent overcurrent
trip (E.OC
첸
).)
Check the capacities of the inverter and the
motor.
—
Regeneration avoidance operation is per-
formed
If the frequency becomes unstable during
regeneration avoidance operation, decrease
the setting of Pr. 886 "Regeneration avoid-
ance voltage gain".
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......