Parameter
Set V/F pattern
FR-E700 SC EC/ENE
6 - 57
Set two kinds of base frequencies (Pr. 47)
Use the second base frequency when you want to change the base frequency, e.g. when using mul-
tiple motors by switching between them by one inverter.
Pr. 47 "Second V/F (base frequency)" is valid when the RT signal is on.
Base frequency voltage setting (Pr. 19)
Use Pr. 19 "Base frequency voltage" to set the base voltage (e.g. rated motor voltage). If the setting is
less than the power supply voltage, the maximum output voltage of the inverter is as set in Pr. 19.
Pr. 19 can be utilized in the following cases:
●
When regeneration frequency is high (e.g. continuous regeneration)
During regeneration, the output voltage becomes higher than the reference and may cause an
overcurrent trip (E.OC
첸
) due to an increased motor current.
●
When power supply voltage variation is large
When the power supply voltage exceeds the rated voltage of the motor, speed variation or motor
overheat may be caused by excessive torque or increased motor current.
NOTES
The RT signal acts as the second function selection signal and makes the other second functions
valid.
Set "3" in any of Pr. 178 to Pr. 184 "Input terminal function selection" and assign the RT signal.
NOTES
When advanced magnetic flux vector control or general-purpose magnetic flux vector control is
selected, Pr. 3, Pr. 47 and Pr. 19 are invalid and Pr. 83 and Pr. 84 are valid.
Note that Pr. 3 or Pr. 47 value is made valid as inflection points of S-pattern when Pr. 29 "Accelera-
tion/deceleration pattern selection" = 1 (S-pattern acceleration/deceleration A).
Changing the terminal assignment using Pr. 178 to Pr. 184 "Input terminal function selection" may
affect the other functions. Make setting after confirming the function of each terminal.
Note that the output voltage of the inverter cannot exceed the power supply voltage.
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......