Communication operation and setting
Parameter
6 - 238
Stop operation selection at occurrence of communication fault (Pr. 502)
●
For FR-E700 SC EC
Stop operation when retry count excess (Mitsubishi inverter protocol only) or signal loss detection er-
ror occurs can be selected.
Pr. 502
Operation
Indication
Fault Output
0 (initial value)
Coasts to stop.
E. PUE lit
Provided
1
Decelerates to stop
E. PUE lit after stop
Provided after stop
2
Not provided
3
Same as the setting "0"
Tab. 6-67:
Operation at fault occurrence
Pr. 502
Operation
Indication
Fault Output
0 (initial value)
Kept stopped
E.PUE
Kept provided
1
2
Automatic restart functions
Normal display
Not provided
3
Same as the setting "0"
Tab. 6-68:
Operation at fault removal
Fig. 6-119:
Operation when Pr. 502 setting is "0 (initial value) or
3"
I001834E
Fig. 6-120:
Operation when Pr. 502 setting is "1"
I001835E
Communication
fault
Display
OFF
Fault
occurrence
Output fr
equenc
y
Fault display
(E.PUE)
Fault output
(ALM)
ON
Fault
removal
Motor
coasting
OFF
ON
OFF
Time
Communication
fault
Display
OFF
Fault
occurrence
Output fr
equenc
y
Fault display
(E.PUE)
Fault output
(ALM)
ON
Fault
removal
Decelerates to
stop
OFF
ON
OFF
Time
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......