Operation panel
Operation
4 - 16
4.3.8
Change the parameter setting value
Possible faults:
●
"Er1" to "Er4" is displayed ... Why?
– The error indication means:
Er1:
Write disable error
Er2:
Write error during operation
Er3:
Calibration error
Er4:
Mode designation error
For details refer to section 7.1.
Example
쑴
Change the Pr. 1 "Maximum frequency" setting from 120 Hz to 50 Hz.
I001462E
Fig. 4-12:
Setting the maximum output frequency
햲
Screen at powering on
The monitor display appears.
햳
Press the PU/EXT key to choose the PU
operation mode.
햴
Press the MODE key to choose the parameter
setting mode.
햵
Turn the digital dial until P.1 (Pr. 1) appears.
햶
Press the SET key to show the currently set value.
The initial value "120.0" appears.
햷
Turn the digital dial counter clockwise to change it
to the setting value of "50.00".
햸
Press the SET key to set.
Operation
Display
The parameter number
read previously appears.
Flicker ... Parameter setting complete!
PU indication is lit.
앫
Turn the digital dial to read another parameter.
앫
Press the SET key to show the setting again.
앫
Press the SET key twice to show the next parameter.
앫
Press the MODE key twice to return the monitor to frequency monitor.
PRM indication is lit.
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......