Communication operation and setting
Parameter
6 - 246
6.19.4
Mitsubishi inverter protocol (computer link communication)
You can perform parameter setting, monitor, etc. from the PU connector of the inverter using the Mit-
subishi inverter protocol (computer link communication).
Communication specifications
Item
Description
Related
Parameters
Communication protocol
Mitsubishi protocol (computer link)
Pr. 549
Conforming standard
EIA-485 (RS-485)
—
Number of inverters connected
1 : N (maximum 32 units), setting is 0 to 31 stations
Pr. 117
Communication
speed
PU connector
Selected from among 4800/9600/19200 and 38400 bps
Pr. 118
Control protocol
Asynchronous system
—
Communication method
Half-duplex system
—
Communication
specifications
Character
system
ASCII (7 bits or 8 bits can be selected)
Pr. 119
Start bit
1 bit
—
Stop bit length
1 bit or 2 bits can be selected
Pr. 119
Parity check
Check (even, odd) or no check can be selected
Pr. 120
Error check
Sum code check
—
Terminator
CR/LF (presence or absence can be selected)
Pr. 124
Waiting time setting
Selectable between presence and absence
Pr. 123
Tab. 6-72:
Communication specifications
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......