Parameter
Parameter overview
FR-E700 SC EC/ENE
6 - 15
Func-
tion
Parameter
Name
Incre-
ments
Initial
Value
Setting
Range
Description
Para-
meter-
Copy
Para-
meter
Clear
All
Para-
meter
Clear
Refer
to
Page
Rela
te
d
Paramet
ers
✔
: Enabled
—: Disabled
Offline aut
o tuning
94
Motor constant (X)
0.1% *
9999
0–100% *
Tuning data (The value measured by offline
auto tuning is automatically set.)
* The range differs according to the Pr. 71
setting.
✔
—
✔
9999
Use the Mitsubishi motor (SF-JR, SF-HRCA)
constants
96
Auto tuning setting/status
1
0
0
Offline auto tuning is not performed
✔
—
✔
1
For advanced magnetic flux vector control
Offline auto tuning is performed without
motor running (all motor constants)
11
For general-purpose magnetic flux vector
control
Offline auto tuning is performed without
motor running (motor constant (R1) only)
21
Offline auto tuning for V/F control
(automatic restart after instantaneous
power failure (with frequency search))
859
Torque current
0.01 A *
9999
0–500 A *
Tuning data (The value measured by offline
auto tuning is automatically set.)
* The range differs according to the Pr. 71
setting.
✔
—
✔
9999
Use the Mitsubishi motor (SF-JR, SF-HRCA)
constants
—
89
Refer to Pr. 81
90
–
94
Refer to Pr. 82 to 84
96
Refer to Pr. 82 to 84
Tab. 6-1:
Parameter overview (15)
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......