Basic settings
Simple mode parameter list
FR-E700 SC EC/ENE
5 - 17
Execution of tuning
When performing tuning or PU operation, press the RUN key of the operation panel or the FWD or REV
key of the parameter unit (FR-PU04/FR-DU07).
For external operation, turn on the run command (STF signal or STR signal). Tuning starts.
E
CAUTION:
Before performing tuning, check the monitor display of the operation panel or parameter unit
(FR-PU04/FR-PU07) if the inverter is in the status for tuning (refer to Tab. 5-4). When the start
command is turned on under V/F control, the motor starts.
NOTES
To force tuning to end, use the MRS or RES signal or press the STOP key of the operation panel.
(Turning the start signal (STF signal or STR signal) off also ends tuning.)
During offline auto tuning, only the following I/O signals are valid: (initial value)
– Input terminal <valid signal> MRS, RES, STF, STR
– Output terminal RUN, AM, A, B, C
Note that the progress status of offline auto tuning is output from AM when speed and output fre-
quency are selected.
Since the RUN signal turns on when tuning is started, caution is required especially when a
sequence which releases a mechanical brake by the RUN signal has been designed.
When executing offline auto tuning, input the run command after switching on the main circuit
power (R/L1, S/L2, T/L3) of the inverter.
Do not perform ON/OFF switching of the second function selection signal (RT) during execution of
offline auto tuning. Auto tuning is not executed properly.
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......