Troubleshooting
Causes and corrective actions
FR-E700 SC EC/ENE
7 - 17
Operation panel
indication
E.RET
FR-PU04
FR-PU07
Retry No Over
Name
Retry count excess
Description
If operation cannot be resumed properly within the number of retries set, this function trips the
inverter. Functions only when Pr. 67 "Number of retries at fault occurrence" is set. When the initial
value (Pr. 67 = 0) is set, this protective function does not function.
Check point
Find the cause of fault occurrence.
Corrective action
Eliminate the cause of the error preceding this error indication.
Operation panel
indication
E. 5
FR-PU04
FR-PU07
Fault 5
E. 6
Fault 6
E. 7
Fault 7
E.CPU
CPU Fault
Name
CPU fault
Description
Stops the inverter output if the communication fault of the built-in CPU occurs.
Check point
앫
Check for devices producing excess electrical noises around the inverter.
앫
Check if the terminal PC is shorted with the terminal SD. (E. 6/E. 7)
Corrective action
앫
Take measures against noises if there are devices producing excess electrical noises around
the inverter.
앫
Check the connection between the terminals PC and SD. (E. 6/E. 7).
앫
Please contact your sales representative.
Operation panel
indication
E.IOH
FR-PU04
FR-PU07
Fault 14
Inrush overheat
Name
Inrush current limit circuit fault
Description
Stops the inverter output when the resistor of inrush current limit circuit overheated. The inrush
current limit circuit fault.
Check point
Check that frequent power ON/OFF is not repeated.
Corrective action
Configure a circuit where frequent power ON/OFF is not repeated. If the problem still persists
after taking the above measure, please contact your sales representative.
Operation panel
indication
E.AIE
FR-PU04
FR-PU07
Fault 14
Analog in error
Name
Analog input fault
Description
Appears if voltage (current) is input to terminal 4 when the setting in Pr. 267 "Terminal 4 input
selection" and the setting of voltage/current input switch are different.
Check point
Check the setting of Pr. 267 "Terminal 4 input selection" and voltage/current input switch.
Corrective action
Either give a frequency command by current input or set Pr. 267 Terminal 4 input selection, and
voltage/current input switch to voltage input. (Refer to section 6.16.1.)
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......