Parameter
Communication operation and setting
FR-E700 SC EC/ENE
6 - 285
Ethernet function selection (Pr. 833 to Pr. 835)
Refer to the Instruction Manual of the device connected via Ethernet, and set Pr. 833 to Pr. 835 Ether-
net function selection1 to 3 according to the application and protocol.
A communication socket is provided only for the selected application.
햲
If both application and protocol settings are identical in Pr.833 to Pr.835, the priority of the set-
ting is defined as follows: Pr. 833 > Pr. 834 > Pr. 835.
(Example) When Pr. 833 = "31", Pr. 834 = "36", Pr. 835 = "20", "20" and "31" are valid.
햳
To establish the Ethernet communication between the inverter and FR Configurator2, set "20" and
"31" in any two of Pr. 833 to Pr. 835.
Communication speed and full-duplex/half-duplex selection (Pr.832)
Set the communication speed and the communication mode (full-duplex/half-duplex) in Pr. 832 Link
speed and duplex mode selection. If the operation is not performed properly in the initial setting
(Pr. 832 = "0"), set Pr. 832 according to the specifications of the connected hub.
Pr.833 to Pr.835 setting
Port
number
Application
햲
Protocol
햲
Number of con-
nectable clients
Refer to
page
0
502
MODBUS®/TCP
TCP/IP
3
10
61450
CC-Link IE Field Network Basic
UDP/IP
No limit
20 (Pr. 834 initial value)
햳
45237
iQSS (supported by FR Configurator2)
UDP/IP
No limit
—
30
5000
MELSOFT / FA product connection
UDP/IP
No limit
31 (Pr. 833 initial value)
햳
5001
UDP/IP
No limit
36
5006
UDP/IP
No limit
38
5008
UDP/IP
No limit
9999 (Pr. 835 initial value) Unselected
—
Tab. 6-108:
Settings for the Ethernet function selection
Pr. 832
Communication
speed
Full-duplex/
halfduplex system
Remarks
0 (initial value)
Automatic negotiation
Automatic negotiation
The communication speed and the communication
mode (half-duplex/full-duplex) are automatically
negotiated to ensure the optimum setting.
1
100 Mbps
Full-duplex
—
2
100 Mbps
Half-duplex
—
3
10 Mbps
Full-duplex
—
4
10 Mbps
Half-duplex
—
Tab. 6-109:
Setting of Pr. 832
Содержание fr-e700 series
Страница 2: ......
Страница 4: ......
Страница 20: ...Contents XVI ...
Страница 112: ...Operation panel Operation 4 20 ...
Страница 154: ...External operation Basic settings 5 42 ...
Страница 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Страница 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Страница 606: ...A 30 Index Appendix ...
Страница 607: ......