Basic settings
Simple mode parameter list
FR-E700 SC EC/ENE
5 - 7
5.1.4
Limit the maximum and minimum output frequency (Pr. 1, Pr. 2)
Pr.
No.
Name
Initial Value
Setting
Range
Description
1
Maximum frequency
120 Hz
0–120 Hz
Set the upper limit of the output frequency.
2
Minimum frequency
0 Hz
0–120 Hz
Set the lower limit of the output frequency.
Example
쑴
You can limit the motor speed. Limit the frequency set by the potentiometer, etc. to 50 Hz maxi-
mum. (Set "50" Hz to Pr. 1 "Maximum frequency".)
Fig. 5-5:
Minimum and maximum output frequency
I001100E
Pr. 1
Pr. 18
Clamped at the
maximum frequency
5, 10 V
(20 mA)
Output
frequency [Hz]
Pr. 2
Frequency
setting
0
(4 mA)
Clamped at the
minimum frequency