Parameter
Limit the output frequency
FR-E700 SC EC/ENE
6 - 53
Set the minimum frequency
Use Pr. 2 "Minimum frequency" to set the lower limit of the output frequency.
NOTES
When Pr. 15 "Jog frequency" is equal to or less than Pr. 2, the Pr. 15 setting has precedence over the
Pr. 2 setting.
The output frequency is clamped by the Pr. 2 setting even the set frequency is lower than the Pr. 2
setting (The frequency will not decrease to the Pr. 2 setting.)
E
CAUTION:
If the Pr. 2 setting is higher than the Pr. 13 "Starting frequency" value, note that the motor will
run at the set frequency according to the acceleration time setting by merely switching the start
signal on, without entry of the command frequency.